Controller 1

The Controller 1 is a 230V AC powered intelligent wireless input/output module, providing one relay output, four digital inputs and two temperature or light sensor inputs.

 

Features

  • High performance wireless with up to 2km line-of-sight range
  • Multi-hop wireless protocol
  • 5A Relay output NO/NC with relay status LEDs
  • Relay output override button
  • 4 × digital inputs configurable for status, alarm or pulse count
  • Digital input status LEDs
  • 2 × thermistor or light sensor inputs
  • Signal test/discovery button

Specification

Temperature & humidity

Operating temperature range -10 to +50°C

Operating humidity 75% RH (Non condensing)

Storage temperature -20 to +85°C

Storage humidity <90% RH (non-condensing)

Cooling Convection

 

Power

Supply voltage 230VAC 50/60Hz

Current consumption 3W (13mA)  

 

Relay

Relay contact rating 5A max @ 230VAC (resistive/inductive load), 5A max @ 30VDC (resistive/inductive load)

Relay mechanical life expectancy 10,000,000 operations min

Relay electrical life expectancy 100,000 operations min (max load)

 

Inputs

Thermistor inputs 10K Thermistor 10K3A1 (Resistive)

Digital inputs ‘Volt-free’ (Internal DC supply used)

 

RF data

RF frequency 433.05 – 434.79MHz

RF output 8dBm max

RF sensitivity -115dBm

RF bandwidth 25kHz (Narrow band)

RF channels 69

Antenna connector Female 50Ω SMA (SubMiniature version A)

 

Misc

Terminal covers UL94-VO, IP20 finger protection

Enclosure UL94-VO flame retardant PC, IP20 rated

Mounting 35mm DIN rail (EN 50022, BS 5584, DIN 46277-3) or direct surface mount. Optional adaptor for G rail mounting  

 

Weight & dimensions

Weight 216g (without antenna)

Width 53mm

Height 90mm

Depth 58mm

Compliance

EMC

EN 301489-1: 2008

EN 55022: 2006

EN 61000-4-3: 2006

EN 61000-4-2: 2001

EN 61000-4-4: 2004

EN 61000-4-5: 2006

EN 61000-4-6: 2005

EN 61000-4-11: 2004

EN 61000-3-3: 1995

Safety

EN 60950: Information technology equipment

EN 60730: Automatic electrical controls

EN 50366: Domestic equipment

Wireless

EU R&TTE directive for 25kHz

EN 300 220:

EMC standard for short range devices

EN 301 489: EMC standard for radio equipment and services

 

Certifications

CE2 ROHS2 

 

Become a partner today