NiagaraAX interface

The wireless interface allows you to use our robust wireless I/O with your NiagaraAX platform. The interface is connected to your platform via Modbus and the driver enables your points to be added within WorkPlaceAX as if they were native wired hardware.

 

Features

  • Transparent serial network wireless ‘bridge’
  • NiagaraAX Framework serial driver which can run on a JACE/Hawk/EC-BOS
  • Connects via Modbus
  • High performance wireless narrow band operation with up to 1km line-of-sight range
  • Status LEDs
  • 12V DC powered

See it in action

Discovering our wireless I/O into WorkPlaceAX couldn’t be simpler. All you need is a licensed version of our Niagara wireless interface and some WEMS wireless I/O. With the interface connected to your JACE via a serial connection, your I/O will appear as native wired points within the WorkPlaceAX environment. See our demo video opposite for a more in-depth, demonstration.

Specification

Temperature & humidity

Operating temperature range -10 to +50°C

Operating humidity <75% RH (Non condensing)

Storage temperature -20 to +85°C

Storage humidity <90% RH (non-condensing)

Cooling Convection

 

Power

Supply voltage 5VDC (regulated) 200mA max

Current consumption 3W (13mA)

 

RF

RF frequency 433.05 – 434.79MHz

RF output 8dBm max

RF sensitivity -115dBm

RF bandwidth 25kHz (Narrow band)

RF channels 69

Antenna connector Female 50Ω SMA (SubMiniature version A)

Misc

Enclosure UL94-VO flame retardant PC, IP20 rated

Mounting 35mm DIN rail (EN 50022, BS 5584, DIN 46277-3) or direct surface mount. Optional adaptor for G rail mounting

 

Weight & dimensions

Weight 216g (without antennas)

Width 53mm

Height 90mm

Depth 58mm

Compliance

EMC

EN 301489-1: 2008

EN 55022: 2006

EN 61000-4-3: 2006

EN 61000-4-2: 2001

EN 61000-4-4: 2004

EN 61000-4-5: 2006

EN 61000-4-6: 2005

EN 61000-4-11: 2004

EN 61000-3-3: 1995

Safety

EN 60950: Information technology equipment

EN 60730: Automatic electrical controls

EN 50366: Domestic equipment

Wireless

EU R&TTE directive for 25kHz

EN 300 220: EMC standard for short range devices

EN 301 489: EMC standard for radio equipment and services

 

 Certifications

CE2 ROHS2